Fieldbus Control Of The Line-Side Converter; Control Block Diagram - ABB ACS800 Hardware Manual

Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

Fieldbus control of the line-side converter

Fieldbus control of the line-side converter can only be performed via the motor-side
converter RMIO board. The control signal dataset receive and actual signal dataset
transmit addresses are shown in section

Control block diagram

The figure below shows the parameters for DC and reactive power reference
selection of the line-side converter control program. The AMC table contains actual
values and parameters of the line-side converter. The control and actual signal
interchange between the line-side and motor-side converters is also shown.
Motor-side
converter RMIO
112.04 SUPPLY CTRL
MODE = LINE CONV
Dataset 121 (CH1)
MCW
95.06 LCU Q POW REF
95.07 LCU DC REF (V)
Dataset 122 (CH1)
MSW
9.12 LCU ACT SIGNAL 1
9.13 LCU ACT SIGNAL 2
Dataset 123 (CH1)
95.08 LCU PAR1 SEL
95.09 LCU PAR2 SEL
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Line-side converter
RMIO board
98.02 COMM. MODULE
= INVERTER
Dataset 121 (CH0)
MCW (fixed)
Q-REF(fixed)
24.02
DC REF(fixed)
Dataset 122 (CH0)
MSW (fixed)
106 (value)
110 (value)
Dataset 123 (CH0)
106
110
MCW = Main Control Word
MSW = Main Status Word
Control block diagram
11.02 Q REF SELECT
PARAM 24.01
24.03 Q POWER REF2 SEL
PERCENT
PARAM 24.02
+
kVAr
+
PHI
COSPHI
24.04
AMC
table
below.
AI1
24.01
AI2
AI3
Q POWER REF
11.01 DC REF SELECT
PARAM 23.01
DC VOLT REF
AI1
23.01
AI2
AI3
FIELD BUS
The ACS800-31/U31
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-31Acs800-u31

Table of Contents