Control panel

The drive is equipped with a control panel (type CDP-312R). The CDP-312R is the
user interface of the line-side converter and the motor-side converter of the drive,
providing the essential controls such as Start/Stop/Direction/Reset/Reference, and
the parameter settings for the units' application programs. More information on using
the panel can be found in the Firmware Manual delivered with the drive.
The control panel is wired to both the line-side converter and the motor-side
converter using a Y-splitter. The converter that is currently being controlled is
indicated by the converter name on the drive display; the suffix "MR" denotes motor-
side converter, "LR" denotes line-side converter. The control is switched between the
converters as follows:

To control the line-side converter...

Step
Action
1.
Enter the Drive Selection Mode.
Note: In local control mode, the motor-side converter trips
if parameter 30.02 PANEL LOSS is set to FAULT. Refer to
the appropriate application program firmware manual.
2.
Scroll to ID number 2.
3.
Verify the change to the line-side converter and display the
warning or fault text .
WARNING! The drive does not stop by pressing the control panel Stop key in local
control mode.
Start-up and use
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Press key
Display (example)
ACS 800 0050_5MR
DRIVE
ASXR7xxx
ID-NUMBER 1
ACS 800 0050_5LR
IXXR7xxx
ID-NUMBER 2
2
ACS 800 0050_5LR
ACT
** FAULT **
DC OVERVOLT
-> 380.0 V
(3210)