Verify that the brown cable (RS485A) of the PID module is connected to Surge port 1 or 7 on
the RS485 signal SPD, and that the black cable (RS485B) is connected to Surge port 5 or 11
on the RS485 signal SPD.
Step 3 Set Baud Rate for the PID module to the same Baud Rate configured for the SmartLogger.
----End
Follow-up Procedure
Take the reverse steps to disconnect the SmartLogger from the PID module.

4.9 Connecting a Ripple Control Receiver

Context
In Germany and some other European areas, a Ripple Control Receiver is used to convert a
power grid scheduling signal to a dry contact signal, in which a dry contact is needed.
Figure 4-30 shows the DI ports of the SmartLogger.
Figure 4-30 DI ports of the SmartLogger
Table 4-8 describes the DI ports.
(2016-06-20)
The baud rates supported by the PID module include 4800 bit/s, 9600 bit/s, 19200 bit/s, and 115200
bit/s.
The PID module supports automatic address allocation. After connecting cables, log in to the WebUI
and search for the PID module in the Connect Device > Auto. Search menu.
For details about PID parameter settings, see PID.
The default RS485 communications address of the PID module is 1. To change the RS485
communications address, log in to the WebUI and follow instructs in Connecting a Device.