Setting and canceling a temporary error invalid station
Even if a data link error occurs in a slave station, the station is not detected as a faulty station in the master station and local
station. This can be set even during data link, unlike the error invalid station setting function.
This function is used to exchange slave stations for maintenance or for other purposes during data link.
■Procedure
1.
Open the "CC-Link Diagnostics" window.
[Diagnostics]  [CC-Link Diagnostics]
2.
Right-click the target slave station icon of the temporary error invalid station setting and select "Enable/Disable Ignore
Station Errors".
The selected station will be a temporary error invalid station.
3.
When the step 2 is performed while the selected station has been set as a temporary error invalid station, the temporary
error invalid station setting is canceled.
When setting a temporary error invalid station, do not write data to the buffer memory areas (buffer memory
address: 5E0H and 603H to 607H).
4 TROUBLESHOOTING
4.3 Checking the System Status
4
111