Mitsubishi Electric MELSEC iQ-R Series User Manual page 54

Melsec iq-r cc-link system master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Precautions
■Reflection of the settings
The initial settings registered using an engineering tool are reflected to a remote device station by writing the settings to a
CPU module and turning on 'Remote device station initialization procedure registration instruction' (SB000D).
■Processing time
Because one step is executed per link scan, more setting items extend the processing time further than that of when a
program is used.
■While 'Remote device station initialization procedure registration instruction' (SB000D) is on
Data in the remote I/O (RX, RY) and remote register (RWr, RWw) stops being refreshed.
■Handling of signals that are required to be always on (such as CH. Conversion enable flag
of an AJ65BT-64RD3/4)
Turning off 'Remote device station initialization procedure registration instruction' (SB000D) after the initial processing is
completed turns off all the RY signals that have turned on while the initial procedure registration is performed. To prevent this,
use a program to turn on signals that are required to be always on.
■Turning on 'Completion status of remote device station initialization procedure' (SB005F)
When 'Specification of remote device station to be initialized' (SW0014 to SW0017) is selected, 'Completion status of remote
device station initialization procedure' (SB005F) does not turn on until the procedure registration is normally completed in all
the stations. If a faulty station exists, turn off 'Remote device station initialization procedure registration instruction' (SB000D)
depending on the completion status of other stations.
■Initialization procedure registration for a standby master station
The initial setting cannot be configured in a standby master station. When replacing a remote device station while a standby
master station is operating as a master station, configure the initial setting on a program.
■When the instruction is not required
The initialization procedure registration instruction may not be required under some situations, such as when the remote input
(RX) is set as a condition device.
Link special relay (SB) areas and link special register (SW) areas
■Link special relay (SB) areas
Link special relay (SB) areas related to the remote device station initialization procedure registration are listed below.
• 'Remote device station initialization procedure registration instruction' (SB000D)
• 'Execution status of remote device station initialization procedure' (SB005E)
• 'Completion status of remote device station initialization procedure' (SB005F)
■Link special register (SW) areas
• 'Specification of remote device station to be initialized' (SW0014 to SW0017)
• 'Remote device station initialization procedure registration instruction result' (SW005F)
• 'Remote device station initialization procedure registration completion status' (SW0164 to SW0167)
Buffer memory
Buffer memory areas related to the remote device station initialization procedure registration are listed below.
• 'Remote device station initialization procedure registration execution individual information' (Buffer memory address:
Un\G23680 to Un\G23743)
1 FUNCTIONS
52
1.4 Remote Device Station Initial Setting Procedure Registration Function