7.
Set the network configuration as follows.
[Navigation window]  [Parameter]  [Module Information]  [RJ61BT11]  [Basic Settings]  [Network Configuration
Settings]
8.
Set the redundant function module of the own system as the system A in the "System A/B Setting" window, and reset the
CPU modules of both systems or power off and on the both systems.
[Online]  [Redundant PLC Operation]  [System A/B Setting]
9.
Write the set parameters to the system A CPU module.
[Online]  [Write to PLC]
10.
Click the [Yes] button to write to the CPU modules of both systems.
11.
Either reset the CPU modules of both systems or power off and on both systems.
In this example, default values are used for parameters that are not shown above. For the parameter setting,
refer to the chapter explaining the parameters in this manual. ( Page 54 PARAMETER SETTINGS)
Appendix 8 How to Use Standby Master Function in Redundant System