Mitsubishi Electric MELSEC iQ-R Series User Manual page 66

Melsec iq-r cc-link system master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Item
1 to 256
Link Side
CPU Side
Precautions
■ Device set to "CPU Side"
Set parameters that differ from the following:
• "Link Refresh Settings" in "Basic Settings" of a CC-Link master/local module
• "Refresh Setting" of other network modules
• I/O numbers used for I/O modules and intelligent function modules
• "Refresh Setting" of intelligent function modules
• "Refresh Setting between Multiple CPU" of "CPU Parameter" for a multiple CPU system
■Use in a redundant system
Do not set a link device other than the link special relay (SB) or link special register (SW) to "Link Side". Setting a link device
other than the link special relay (SB) or link special register (SW) will not result in a refresh.
2 PARAMETER SETTINGS
64
2.3 Basic Settings
Description
Set the link refresh ranges of RX, RY, RWr, and RWw. Up to 256 ranges can
be set. ( Page 27 Link refresh)
Ex.
0000H
Device
·
name
(RX)
00FFH
0000H
Device
·
name
(RY)
00FFH
0000H
Device
·
name
(RWr)
00FFH
0000H
Device
·
name
(RWw)
00FFH
Master/local module
Transfer
1000H
1
Device
·
name
(X)
10FFH
Transfer
1000H
2
Device
·
name
(Y)
10FFH
Transfer
000000H
3
Device
·
name
(W)
0000FFH
Transfer
001000H
4
Device
·
name
(W)
0010FFH
CPU module
Setting range
Device Name
• RX, RY, RWr, RWw
(Default: Blank)
Points
• RX, RY: 16 to 8192 (Set it in increments of 16
points.)
• RWr, RWw: 4 to 2048 (Set it in increments of 4
points)
(Default: Blank)
Start
• RX, RY: 00000H to 01FF0H (Set a multiple of
16 including 0.)
• RWr, RWw: 00000H to 007FCH (Set a multiple
of 4 including 0.)
(Default: Blank)
End
• RX, RY: 0000FH to 01FFFH (Set a multiple of
16 - 1.)
• RWr, RWw: 00003H to 007FFH (Set a multiple
of 4 -1.)
(Default: Blank)
Target
• Specify Device
Device Name
• Specify Device (when link side is RX): X, M, L,
B, D, W, R, ZR, RD (only X, W, and RD for
remote head module)
• Specify Device (when link side is RY): Y, M, L,
B, D, W, R, ZR, RD (only Y, W, and RD for
remote head module)
• Specify Device (when link side is RWr): M, L, B,
D, W, R, ZR, RD (only W and RD for remote
head module)
• Specify Device (when link side is RWw): M, L,
B, D, W, R, ZR, RD (only W and RD for remote
head module)
(Default: Blank)
Points, Start, End
• Range of the device in the CPU module
(Default: Blank)