Mitsubishi Electric MELSEC iQ-R Series User Manual page 132

Melsec iq-r cc-link system master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error details and causes
code
BBCAH
Multiple standby master stations exist on the same line.
BBCBH
System error
BBD1H
System error
BBD3H
System error
BC01H
A data link error has occurred on all stations during a
message transmission.
BC02H
System error
BC03H
The target station specified for the message transmission
function is in any of the following status.
• No network parameter is set.
• The specified station number is not the start station
number.
• The station is set as a reserved station.
• A data link error has occurred (including error on all
stations).
BC04H
The message transmission was performed to a station
other than a remote device station or intelligent device
station.
BC05H
The target station number specified for message
transmission function is not within 1 to 64.
BC06H
The message transmission function was attempted to be
executed on a station other than the master station.
BC07H
The transmission data size was out of the range when
message transmission function was executed.
BC08H,
System error
BC09H
BC33H to
System error
BC39H
BC50H
With the message transmission function, an abnormal data
was received.
BC51H
• During execution of message transmission function, a
data link error has occurred on the corresponding
station.
• During execution of message transmission, some
parameters were changed.
• With the message transmission function, an abnormal
data was received.
BC52H
• With the message transmission function, a
communication timeout has occurred.
• 'Data link stop' (SB0002) was turned on during message
transmission.
• With the message transmission function, a stop error in
the CPU module was detected.
BC53H
• With the message transmission function, a
communication timeout has occurred.
• 'Data link stop' (SB0002) was turned on during message
transmission.
• With the message transmission function, a stop error in
the CPU module was detected.
BC54H
With the message transmission function, an abnormal data
was received.
4 TROUBLESHOOTING
130
4.6 List of Error Codes
Action
• Reduce the number of standby master stations on the
same line to one.
• Check the line status.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Issue the request after the data link is started.
Please consult your local Mitsubishi representative.
Check the parameters or operation on the target station.
Check the target station.
Check the specified station number.
Execute the message transmission function on the master
station.
Set the transmission data size within the range.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Check the program to see if any prohibited remote output
(RY) has not been accessed. If the error occurs again even
after checking the above, the possible cause is a failure of
a master/local module or remote device station. Please
consult your local Mitsubishi representative.
• Check the operation of the target remote device station.
• Stop the data link then change the parameters.
• Check the program to see if any prohibited remote
output (RY) has not been accessed. If the error occurs
again even after checking the above, the possible cause
is a failure of a master/local module or remote device
station. Please consult your local Mitsubishi
representative.
• Set a larger value in 'Monitoring time setting' (SW0009) If
the error occurs again, check the modules and cables at
the destination.
• Stop data link after completion of message transmission.
• To execute message transmission while there is a stop
error in the CPU module, set "Data Link Setting at CPU
Failure" under "Supplementary Cyclic Settings" in
"Application Settings" to "Continue the Data Link".
• Set a larger value in 'Monitoring time setting' (SW0009) If
the error occurs again, check the modules and cables at
the destination.
• Stop data link after completion of message transmission.
• To execute message transmission while there is a stop
error in the CPU module, set "Data Link Setting at CPU
Failure" under "Supplementary Cyclic Settings" in
"Application Settings" to "Continue the Data Link".
Execute the message transmission function again. If the
error occurs again, the possible cause is a failure of a
master/local module or remote device station. Please
consult your local Mitsubishi representative.