PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
02
03
Too high a quartz frequency
difference between A and B:
CPU error
Additional info. 1:
Quartz monitoring
counter A
Additional info. 2:
Quartz monitoring
counter B
02
04
User times cannot be
updated:
PL or CPU error
Additional info. 1:
Sum in A /10msec.
Additional info. 2:
Sum in B /10msec.
B-2
Possible Cause
Error group No. 20
-
More than a 10 % difference
between the CPU quartz
frequencies in A and B
Error group No. 20
More than 30 msec. difference
between the sum of the user time
decrements of a PC cycle in A and B:
-
PL error
-
CPU error
S5-115F Manual
Remedy
-
Replace CPU
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace PL
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
EWA 4NEB 811 6149-02