PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
109
16
Acces to interrupt register
outside OB2:
Programming error
109
17
L PW operation on odd word
address:
Programming error
Additional info. 1:
Word No.
109
18
T PW operation on odd word
address:
Programming error
Additional info. 1:
Word No.
109
19
Nonconfigured interrupts
programmed
109
20
Interrupt with wrong edge
programmed
B-72
Possible Cause
Error group No. 12
Wrong access on DI 434 interrupt-
generating module
Error group No. 1
-
2 I/O words with different
configuration not permitted
-
Configuring error
Error group No. 12
-
2 I/O words with different
configuration not permitted
-
Configuring error
Error group No. 12
-
User program in OB 21/OB 22
enables nonconfigured interrupts
for 434 interrupt module
Error group No. 12
-
User program in OB 21/OB 22
defines rising edge for current
enabled interrupt DI bits
S5-115F Manual
Remedy
-
Remove programming error
Warm restart:
1. Stop/Run
-
Check address for L PW
operation
-
Check configuration of I/O
modules
Warm restart:
1. Stop/Run
-
Check address for T PW
operation
-
Check configuration of I/O
modules
Warm restart:
1. Stop/Run
-
Check interrupt enable for
434 interrupt module in OB
21/OB 22
Warm restart:
1. Stop/Run
-
Check process interrupt edges
of currently enabled interrupt
DI bits for missing edge
(="0")
Warm restart:
1. Stop/Run
EWA 4NEB 811 6149-02