Siemens SIMATIC S5 Manual page 325

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
106
03
PG interface in 115F
operating system faulted:
CPU HW error
Additional info. 1:
R2 (Register bank 3)
Additional info. 2:
R3 (Register bank 3)
Additional info. 3:
R4 (Register bank 3)
Additional info. 4:
R5 (Register bank 3)
Additional info. 5:
R6 (Register bank 3)
106
04
G DB operation on error DBs
(DB 2, 3) not permissible:
programming error
Additional info 1:
DB No.
Additional info 2:
DB length
107
01
SINEC L1 traffic disturbed:
SINEC L1 HW or CPU HW error
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 01
Error group No. 12
Error group No. 11
-
Transceivers defective
-
Bus cables to PC or CP530
interface not plugged in
-
Master CPU or CP530 defective
-
Slave CPU defective
PLC Error Messages
Remedy
-
Replace CPU
Warm restart:
1.
POWER OFF/ON
2.
Stop/Run
-
Check user program
Warm restart:
1.
Stop/Run
-
Replace transceivers
-
Check bus connections
-
Replace Master CPU or CP530
-
Replace Slave CPU
Warm restart:
1. Stop/Run