S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
109
14
Interrupt DI module in A
different to B, discrepancy
time-out
E.g.
Additional info. 1:
DI byte No.
Additional info. 2:
CH DQ byte No.
Additional info. 3:
Bit No.
109
15
Undefined interrupt:
CPU HW error
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 09
I/O comparison, individual error
Error group No. 08
I/O error burst
(only in the case of CPU 942-7UF13
with I/O ETV 3 or 4)
Interrupt DI module comparison
error:
-
Interrupt module defective
-
Process interrupt signals too
frequent (Interrupt interval
< 30msec.)
Error group No. 1
Interrupt >< ZYK, NAU, ALARM
INTA-N
-
CPU HW error
-
Undefined interrupt in CPU
PLC Error Messages
Remedy
-
Replace module
-
Reduce interrupt burst
Warm restart in signal group
No. 0 (Stop mode):
1. Stop/Run
Warm restart in the case of
individual error and signal group
No. 1 to 28
(passivation):
a) Test mode:
1. POWER OFF/ON
2. Stop/Run
b) Safety mode:
1. OVERALL RESET
Warm restart in the case of error
burst:
1. Power OFF/ON
2. Stop/Run
This does not cancel passivation.
To do so, see above: Warm
restart in the case of passivation.
-
Replace CPU
-
Impermissible module
connected (intelligent I/O)
Warm restart:
1. POWER OFF/ON
2. Stop/Run