S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
250
15
FB250 call with wrong
parameters:
Programming error
250
16
Lower wire-break limit value
> upper wire-break limit
value:
Programming/configuring
error
Additional info. 1:
Lower wire-break limit value
Additional info. 2:
Upper wire-break limit value
250
17
AI address configured as
CP 523:
Configuration error
Additional info 1:
AI address
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 12
Substitution error
Error group No. 12
-
Programming error: FB ANEI
wrongly initialized
-
Configuring error: global upper
and lower wire-break limit
wrongly configured
Error group No. 12
Module address specified has been
configured as CP 523
PLC Error Messages
Remedy
Correct the actual FB250 call
parameter (analyze ISTACK)
Warm restart:
1. Stop/Run
-
Check FB ANEI parameters
"DOGR" and "DUGR"
-
Check global wire-break limits
Warm restart:
1. Stop/Run
-
Check FB 250 ANEI call
-
Check configuration
Warm restart:
1. Stop/Run
B-79