PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
25
01
Wrong initial address RAM
area:
CPU error
Additional info. 1:
SD 36
25
02
No. of loaded DB
configured programmer
operator DB No.:
handling error
Additional info. 1:
Operated DB No.
Additional info. 2:
DB address
25
03
Parameter operator DB
configured and not loaded
Additional info 1:
DB No.
Additional info 2:
DB address
B-12
Possible Cause
Error group No. 13
-
CPU error
Initial address of RAM area from
system data,
hex display
Error group No. 16
<>
DB number of the loaded PG entry
DB, decimal display
RAM address of the loaded PG entry
DB,
hex display
Error group No. 16
DB number of PG operator DB called,
decimal display
RAM address of the PG entry DB
called, hex display
S5-115F Manual
Remedy
- Replace CPU
- Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
Change PG entry DB number
or
read in DB
Warm restart:
1. Stop/RUN
Generate parameter entry DB and
load into PC
Warm restart:
1. Stop/Run
EWA 4NEB 811 6149-02