PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
109
09
FB call with wrong
parameter: Programming
error
109
10
Block stack overflow,
Nesting depth > 16:
Programming error
109
11
Undefined STEP 5 operation
(NNN): Programming error
109
12
STS operation in user
program: Desired PLC stop
109
13
Transfer error (TRAF),
Parameter > number of DB
words: Programming error
B-70
Possible Cause
Error group No. 12
Substitution error (SUF) during FB
call in user program
Error group No. 12
-
Maximum block call nesting in
user program exceeded
Error group No. 26
-
Uncoded operation
-
Nesting levels exceeded
-
Parameters exceeded
Error group No. 26
-
SW stop by statement
-
SW request from PG or SINEC L1
master
Error group No. 12
Transfer error:
-
Programmed DB operation:
* DW No. > DB length
* DB opening forgotten
S5-115F Manual
Remedy
-
Correct function block call
(analyze ISTACK)
Warm restart:
1. Stop/Run
-
Remove programming error
(BSTACK, ISTACK)
Warm restart:
1. Stop/Run
-
Remove programming error
(BSTACK, ISTACK)
Warm restart:
1. Stop/Run
Warm restart:
1. Stop/Run
-
Remove programming error
Warm restart:
1. Stop/Run
EWA 4NEB 811 6149-02