Siemens FDA241 Technical Manual page 107

Aspirating smoke detector
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Pipe system
Monitored surface
Compatibility (FDCC221S installed)
Ambient conditions
Mechanical data
Standards
Building Technologies
Fire Safety
Pipe outer diameter
Inner diameter of pipe
Maximum piping lengths for FDA241:
Single line
Branched lines
Maximum piping lengths for FDA221:
Single line
Branched lines
The maximum permissible surface depends on the locally valid regulations!
Maximum surface:
FDA241
FDA221
Compatible with fire control panels
Operating temperature
Storage temperature
Air humidity
Protection category (IEC 60529):
FDA241
FDA221
Weight
Housing material
Housing color
European standards
Specifications
Technical data for FDA241, FDA221
25 mm
21 mm
FDA241: 60 m
FDA241: 2 x 60 m
30 m
2 x 25 m
800 m²
500 m²
FC20xx/FC72x
-20...+60 °C
-30...+70 °C
5...95 % rel.,
no moisture
condensation
IP30
IP30
approx. 1.5 kg
ABS/PC
∽RAL 9010 pure white
EN 54-20 A, B, C
EN 54-17 with
FDCC221S installed
A6V10334410_h_en_--
9
107
2015-09-29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fda221

Table of Contents