Siemens FDA241 Technical Manual page 57

Aspirating smoke detector
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Building Technologies
Fire Safety
Cable entry
Position of hole
Breakthrough on rear
Breakthrough on left side of housing
Breakthrough on top of housing
If the aspirating smoke detector is installed rotated by 180°, the circular
breakthroughs are found on the bottom at the right-hand side.
25 mm
25 x 100 mm
20 mm
110 mm
Cable entry with standard installation position
To prepare the electrical connections, perform the following steps:
1. Break through the necessary cable entries (e.g., using a screwdriver).
2. Attach the plastic cable entries (usual size M20) to the housing.
3. Insert the cables through the relevant cable entries.
See also
 Adapting the front indicator to the installation position [➙ 58]
 Technical data for FDA241, FDA221 [➙ 105]
Mounting / Installation
Preparatory work
Size of hole
25 x 100 mm
Diameter 25 mm
Diameter 25 mm
A6V10334410_h_en_--
5
57
2015-09-29