Mounting / Installation
5

Mounting

5.2
5.2.1
58
Building Technologies
Fire Safety
Mounting

Adapting the front indicator to the installation position

The aspirating smoke detector can be installed rotated by 180° if required. The
front indicator must then also be installed rotated by 180°.
1
Adapting the front indicator to the installation position
 The housing cover has been removed (step 1).
1. Loosen the 8 screws on the inside of the housing cover (step 2).
2. Rotate the front indicator by 180° (step 3).
3. Fasten the front indicator to the housing cover using the 8 screws (step 4).
 The front indicator is adapted to the installation position.
2
3
180°
8x
4
8x
A6V10334410_h_en_--
2015-09-29