Siemens FDA241 Technical Manual page 98

Aspirating smoke detector
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Maintenance / Repair
8
Carrying out water trap maintenance
98
Building Technologies
Fire Safety
Example of how to arrange a water trap
→ →
Airflow
1
Aspirating smoke detector with front
indicator that is rotated by 180°
2
T-fitting for connecting the water trap at a
low horizontal point within the pipe system
3
Distance between manifold and surface of
the water > 300 mm
4
Valve for draining condensation water
5
Outlet opening
6
Condensation water
A6V10334410_h_en_--
2015-09-29