Mounting / Installation
5

Installation

5.3
5.3.1
64
Building Technologies
Fire Safety
Installation
CAUTION
Electrical voltage on lines
Risk of injury due to electric shock
During mounting and installation work, electrical voltage must not be applied
to the lines.
Note the positive and negative poles.
Only connect one wire per terminal. This is the only way to ensure the connection
is failure-free for the entire service life of the device.

Connecting the external power unit

Two connection terminals are available for the aspirating smoke detector's power
supply. This allows more aspirating smoke detectors to be connected to a power
unit.
Prerequisite: The power unit used satisfies the requirements according to the
'External power unit and batteries' chapter.
Connection diagram for 'one aspirating smoke detector on one power
unit'
Connection without forwarding to other aspirating smoke detectors
Connection diagram for 'multiple aspirating smoke detectors on one
power unit'
Connection with forwarding to other aspirating smoke detectors
IN Connection of external power unit
OUT Connection for the power supply of other aspirating smoke detectors
Properties
Protected against polarity reversal
Connection of more aspirating smoke detectors