Siemens FDA241 Technical Manual page 65

Aspirating smoke detector
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Building Technologies
Fire Safety
Procedure
 A suitable external power unit is available.
 The aspirating smoke detector's housing cover is removed.
1. Before connecting the external power unit to the terminal block, check the
voltage provided by the power unit. Permissible value: DC 24 V ±4 V
2. Connect the power unit to the aspirating smoke detector(s) according to the
connection diagram shown.
 The external power unit is connected to the aspirating smoke detector(s).
See also
 External power unit and batteries [➙ 31]
 Power supply kit A (70 W) FP120-Z1 [➙ 37]
Mounting / Installation
Installation
A6V10334410_h_en_--
2015-09-29
5
65