Siemens Cerberus CS1140 Manual page 144

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

E3G060 Control module "monitored" (Part No 542539)
35.4
Important components
144
Building Technologies
Fire Safety & Security Products
(Part No 542539)
1
2
3
4
5
ASIC
ST1
I-BUS
Y11
6
S2
ON
F19
7
1
1
K2
K3
2
4
1
8
K1
9
4
Legend:
1
Programming switch "S7" & "S8": Horn mode setting
constant horn output (factory setting)
intermitted horn output for all horns with internal oscillator (1sec. on
/ 1sec. off)
horns driven by other E3G060 cards can be synchronized, by
through contacting K2 plug contacts
external oscillator input to drive all horns in intermitted mode with
external oscillator
not used
Note: Switch "S7" defines global horn mode for all horn outputs. Invert this mode
(constant / intermitted) individually for each horn output by connecting common
(X1-1) with corresponding control input (X1-15.. 20).
2
Emergency operation –> Programming switch "S6": Allocation activation by
"Emergency operation mode"
If required, the 6 control lines can also be activated even if an alarm is given during
system malfunction (emergency operation). This function can be selected for each
control line via the "S6" programming switch.
Affiliation:
"S6-1" = Control line 1...
"S6-6" = Control line 6
"OFF" Position = Control line is activated in "Emergency operation mode"
S7
S8
ON
S6
1
1
ON
S3
X11
X12
Y12
11
10
Function
F1
F3
F5
F7
H1
F9
F11
H6
13
12
Programming switch
S7
S8
const. Horn
int. osci
inter. Horn
int. osci
inter. Horn
ext. osci
const. Horn
ext. osci
001260_k_en_--.doc
02.2005

Hide quick links:

Advertisement

Table of Contents
loading