K3R071 Mimic Display Board (Superseded By K3R072) - Siemens Cerberus CS1140 Manual

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

49
K3R071 Mimic Display board
49.1
Overview
49.2
Application
Synoptic display panel housing
49.3
Key data
Building Technologies
Fire Safety & Security Products
Option to control console AlgoPilot B3Q... or to LON/Mimic Display converter
K3I050
Enables the activation of LEDs for Mimic display panels
48 short-circuit proof outputs on connectors for LED activation
2 control outputs for local 'Buzzer' and 'LED' operation
2 inputs for 'Switch-off buzzer' and 'Lamp test'
The lamp test is integrated in menu function AlgoPilot
Individual allocation of the individual outputs
Max. 24 units, however max. 8 addresses
Communication is via a special serial bus
Line and device not monitored
The Mimic Display board is built into the Mimic Display panel housing.
Connection to Mimic Display LED by means of 2-wire cable with connector, a-
vailable as cable set Z3I520 containing 12 pieces
Line length data bus AlgoPilot –> K3R071 max. 1000 m
Connection line
Data bus:
via flat cable or 6-wire cable
Supply 24 V:
via 3-wire cable
Short-circuit proof in-/outputs only for inside housing appli-
cation
max. permissible length of the data bus 1000 m
1) LED 1...48
1
2
2) Key 'Switch-off buzzer'
3
3) Key 'Lamp test'
4
4) Buzzer
5
5) LED operation
Operating voltage
Current consumption
at 24 V
at 9 V
at 45 V

K3R071 Mimic Display board (superseded by K3R072)

(superseded by K3R072)
These in-/outputs can be in
parallel with other K3R071 if
located in same cabinet
9..45 VDC
quiescent 40 mA
max. 140 mA
quiescent 80 mA
max. 330 mA
quiescent 30 mA
max. 90 mA
AlgoPilot
207
001260_k_en_--.doc
02.2005