E3G060 Control module "monitored"
35.1

Overview

35.2
Application
35.3
Key data
Building Technologies
Fire Safety & Security Products
Control module for monitored alarm devices
6 monitored control lines 24 V, 2 A with EMI and over voltage protection
Individual allocation of control lines via maintenance PC (AlgoWorks)
It is possible to specify separately whether or not each line must be activated in
"Emergency alarm" mode (programming switch "S6")
Drive horns by internal or external oscillator (intermitted Horn output)
Max. 8 x E3G060 cards per system (synchronized over plug-in terminal K2)
Ground fault monitoring, detected via master module E3X10. (for application de-
tails see chapter 6)
Card format 100 mm x 200 mm
I-Bus address is set at programming switch "S3"
the E3G060 module is required in systems with more than 2 monitored control
lines for alarm / or similar equipment
the current on one control line may not exceed 2 A; however, the total current for
all 6 control lines may not exceed 4 A (internal supply K1)
Control outputs
number
max. load
termination resistor
Quiescent current at 24 V
1) Output at same voltage range as from the external supply (K3)
Terminal block X1 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis
E3G060 Control module "monitored" (Part No 542539)
6
2 A each at 20.. 30 V; total 4 A (internal supply, K1)
2 A each at 24 V 1); total 12 A (external supply, K3)
4.75 kΩ
25 mA (no control line active)
(Part No 542539)
001260_k_en_--.doc
02.2005
143