B2F020 Converter

13.1
Overview
13.2
Key data
Building Technologies
Fire Safety & Security Products
Converts the Mains voltage to the system voltage
Consistent with the battery-charging function units E3X10. and E3C...
Designed for an output current of 6 A at 29.6 VDC
Requires no special cooling
Built-in thermal fuse
Current limited
Short circuit proof
Parallel operation
Switches on primary side
With metal shielding
Dimensions 200 x 100 x 40 mm
Power supply general
The power supply for the CS1140 series of fire detection system control units con-
sists of the following three components:
Converter B2F020
Battery-charging function unit either as an integrated component in the
E3X10. (for details see E3X10.) or as a separate battery-charging module E3C...
(for details see E3C...)
Emergency power battery, capacity according to quiescent current and the re-
quired mains autonomy; see document 1076 (EP5), 008725 (EP7F-Z1) "Emer-
gency power calculation")
Over voltage protection
Additional surge protectors are only necessary in Special cases e.g. where there
is a particular risk from lightning, overhead mains lead etc. (see Z3I041, Z3I121 –>
page 76)
Mains voltage
Power consumption
Mains fuse
Output current
Output voltage
Residual ripple
Quiescent current with battery operation 0 mA
Temperature range
Standard
115 / 230 VDC +10 %/–15 % 50...60Hz
40...320 VA
3.15 A/T, permanently integrated, not exchangeable on site
max. 6 A continuous (limited)
29.6 VDC +/–2 %
max. 300 mVpp
0...+70 °C without ventilator,
automatic switch-off at > 90 °C
CE / prEN54-4
B2F020 Converter