Siemens Cerberus CS1140 Manual page 34

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

E3X100 Master module (superseded by E3X101)
34
Building Technologies
Fire Safety & Security Products
21
Fuses
F1
630 mA/T
F2
63 mA/T
F5, F6
2 A/T*
F7, F8
2 A/T*
F9
2 A/T*
F10
2 A/T*
F11
2 A/T*
F12
2 A/T*
F13, F14
2 A/T*
F15, F16
2 A/T*
F17...F25
0,5 A/T*
F26
2 A/T*
F27
2 A/T*
F28...F32
2 A/T*
F501...F503
6,3 A/T*
* Fuse with high breaking capacity
Supply 5 V/12 V
Auxiliary supply ASIC
Control line alarm horn 1
Control line alarm horn 2
unused
Emergency operation circuit "Silence horn"
Emergency operation circuit "Common"
Emergency operation circuit "Fire alarm"
Supply "Control console B3Q..." +
Supply "Control console B3Q..." –
Programmable control outputs "Q1...Q8"
Supply "Remote transmission"
Supply "Reserve"
Programmable control inputs "I1...I4"
Battery (F501 "Positive" / F502 "Negative" / F503 "Centre")