52

K3I050 LON/Mimic Display converter

52.1
Overview
52.2
Application
52.3
Key data
52.4
Wiring principle
E3I040
24VDC
Building Technologies
Fire Safety & Security Products
convert LON-Bus to Data bus for Mimic Display drivers K3R071/072 or parallel
indicator panels B3R051
LON-Bus device
Max. 32 units
Connectable via flat cable or adapter Z3I530 up to 24 units K3R071/072 or
B3R051, however max. 8 addresses only
Inputs for key 'buzzer off' and key 'lamp test'
Outputs for buzzer and LED 'system on'
Board format 100 mm x 200 mm
Equipped with mounting plate
Required to run K3R071/072 and B3R051 via LON-Bus
Operating voltage
Current consumption
ratings
output buzzer
output LED state ON
LON-Bus
K3I050
X6
X7
X8
X9
Lamp test
Buzzer
key
Operation
LED
Buzzer off
key
K3R071/072, B3R051 used via K3I050: In the event of a communication break
(LON-Bus or I-Bus) the K3I050 sets all LED outputs to the state 'inactive' and
activates the output 'buzzer'
Output 'buzzer'
active: a) steady if any LED output within the K3R071/072, B3R051 is initiated
b) intermittent in case of a communication break
remains active until input 'buzzer OFF' is activated or the cause for a) or b) no
longer exists
Input 'lamp test'
Activates all LED outputs within the K3R071/072, B3R051 for approx. 2 sec.
9..45 VDC
at 24 V
quiescent 15 mA
max. 30 mA
at 9 V
quiescent 30 mA
max. 50 mA
at 45 V
quiescent 15 mA
max. 30 mA
max. 50 mA / 22 VDC
3.3 VDC / 10 mA
max. length of connection from K3I050 to the last device: 1000 m
K1
ST2
Data bus
24VDC
K3R071/072
or
B3R051
K3R071/072
or
B3R051
K3I050 LON/Mimic Display converter
B3Q590/
B3Q580
1
24
001260_k_en_--.doc
595
221
02.2005