K3R072 Mimic Display board (supersedes K3R071)

50
K3R072 Mimic Display board
50.1
Overview
50.2
Application
Synoptic display panel housing
50.3
Key data
212
Building Technologies
Fire Safety & Security Products
Option to control console AlgoPilot B3Q..., or to LON/Mimic Display converter
K3I050
2x24 outputs for LED activation for Mimic Display panels, or not monitored relay
contacts (K3G060)
2 control outputs for local 'Buzzer' and 'LED operation'
2 inputs for 'Switch-off buzzer' und 'Lamp test'
The lamp test is integrated in menu function AlgoPilot
Individual allocation of the individual outputs
Max. 24 units, however max. 8 addresses
Communication is via a special serial bus
Line and device not monitored
The Mimic Display board is built into the mimic panel housing.
Connection to LED via flat cable F50F410 (50-wire, 24 red LEDs, cable length
1 m, must be ordered separately)
The relay card K3G060 can be connected instead of LEDs
Line length data bus AlgoPilot –> K3R072 max. 1000 m
Connection line
Data bus:
via flat cable or 6-wire cable
Supply 24 V:
via 3-wire cable
Short-circuit proof in-/outputs only for inside housing appli-
cation
max. permissible length of the data bus 1000 m
1) LED 1...24 –> wires 49+50 for 'LED operation'
1
2) LED 25...48 –> wires 49+50 unused
2
3) Key 'Switch-off buzzer'
3
4) Key 'Lamp test'
4
5) Buzzer
5
6
6) Use Z3I520
Operating voltage
Current consumption
at 24 V
at 9 V
at 45 V
(supersedes K3R071)
These in-/outputs can be in
parallel with other K3R072 if
located in same cabinet
9..45 VDC
quiescent 40 mA
max. 140 mA
quiescent 80 mA
max. 330 mA
quiescent 30 mA
max. 90 mA
AlgoPilot