Solar panel installation

The solar panel is designed for outdoor mounting on a 2" extension pipe installed on the upper end of the XRC
pipe. The Solar panel must be mounted within 12 feet of the XRC
XRCG4, it can be mounted on the top or side of the meter house.
NOTICE – Property damage. Do not connect solar panel power cable to the XRC
has been connected to J16.
If installation procedures are required for mounting the solar panel on the top or side of the meter house, the user should contact
Totalflow's Service Department; go to section 5.5, Getting technical support help for additional information.
Materials supplied
One solar panel
Two U-Bolts and fastening hardware
Solar panel cable (standard is 12', other lengths are available)
Solar panel mounting bracket (if not already attached to solar panel)
Customer-supplied materials
Cable ties
One 9-inch extension of 2-inch pipe or other suitable length of pipe, threaded on one end.
One 2-inch coupling.
NOTICE – Property damage. Exercise caution when installing the solar panel, so as not to damage it. When
mounted, the solar panel will face up from the horizon at a 50° angle.
J18 I/O EXP
BATTERY
CONNECTION

Figure 34: Battery and charger input connections

G4
32
J16
CHARGER
INPUT
J17
J6
(other cable lengths are available). For wall-mounted
40" mounting
G4
G4
unless the main battery pack