Siemens SINAMICS S120 Equipment Manual page 31

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Environmental conditions
Degree of protection
Protection class for network current circuits
Protection class for electronic circuits
Permissible coolant temperature (air) and installation
altitude during operation
Chemically active substances
Long-term storage in the transport packaging
Transport in the transport packaging
Operation
Biological environmental conditions
Long-term storage in the transport packaging
Transport in the transport packaging
Operation
Vibratory load
Long-term storage in the transport packaging
Transport in the transport packaging
Operation
Shock load
Long-term storage in the transport packaging
Transport in the transport packaging
Operation
Climatic environmental conditions
Long-term storage in the transport packaging
Transport in the transport packaging
Operation
Certificates
Declarations of Conformity
Approvals
Booksize Power Units
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
IP20 or IPXXB to EN 60529,
open type to UL508
I (with protective conductor connection) and
III (protective extra low voltage DVC A / PELV) acc. to
EN 61 800-5-1
0 °C to +40 °C and an installation altitude of up to 1000 m
without derating,
>40 °C to +55 °C see the characteristic for current derating.
Installation altitude >1000 m up to 4000 m see characteristic
for current derating or reduction of the ambient temperature
by 3.5 K per 500 m.
Class 1C2 to EN 60721-3-1
Class 2C2 to EN 60721-3-2
Class 3C2 to EN 60721-3-3
Class 1B1 to EN 60721-3-1
Class 2B1 to EN 60721-3-2
Class 3B1 to EN 60721-3-3
Class 1M2 to EN 60721-3-1
Class 2M3 to EN 60721-3-2
Test values:
Frequency range: 10 Hz to 58 Hz
With constant deflection of 0.075 mm
Frequency range: 58 Hz to 200 Hz
With constant acceleration of 1 g
Class 1M2 to EN 60721-3-1
Class 2M3 to EN 60721-3-2
Test values: 15 g / 11 ms
Class 1K4 to EN 60721-3-1
Temperature -25 °C to +55 °C
Class 2K4 to EN 60721-3-2
Temperature -40 °C to +70 °C
Class 3K3 to EN 60721-3-3
Temperature +0 °C to +40 °C
Relative / absolute humidity 5 % to 90 % / 25 g/m
Oil mist saline fog, icing, condensation, dripping water,
spray water, splash water and jet water not permissible.
CE (Low Voltage and EMC Directives)
cULus
System Overview
1.7 System data
.
3
31