Line Modules Booksize

3.7 Smart Line Modules (5 kW und 10 kW) with external air cooling

3.7
Smart Line Modules (5 kW und 10 kW) with external air cooling
3.7.1

Description

The Smart Line Module is an unregulated infeed/regenerative feedback unit. The Smart Line
Module supplies the Motor Module(s) with an unregulated DC voltage at the DC output. In
the infeed mode the Smart Line Module exhibits the typical current and voltage waveforms of
a 6-pulse diode rectifier bridge.
In feedback mode, the current waveform is square waved. Feedback can be deactivated by
means of a terminal because these Smart Line Modules are not equipped with a DRIVE-
CLiQ connection.
The DC link starts precharging as soon as the supply voltage is applied and is independent
of its phase sequence direction. Load can be applied to the DC link after the modules have
been enabled. An optional main contactor is required for disconnecting the voltage.
Smart Line Modules are suitable for direct operation in TN, IT, and TT systems. The Line
Modules have an integrated overvoltage protection function.
External air cooling uses the "through-hole" method. This is a cooling method for SINAMICS
power units that is only available for booksize devices. The power unit and its heat sink can
be inserted in a rectangular knockout at the rear of the control cabinet and mounted with a
seal. The heat sink and the fan (included in the scope of supply) project beyond the rear of
the control cabinet and the heat is dissipated outside the control cabinet or in a separate air
duct.
3.7.2

Safety information

Risk of electric shock. A hazardous voltage is present for 5 minutes after the power supply
has been switched-off.
It is only permissible to open the protective cover after this time has expired.
When opening the protective cover for the DC link, you must activate the release.
A suitable tool (e.g. screwdriver) must be used for this purpose.
The components must only be operated when the protective cover of the DC link is closed.
Damaged components must not be used further, as this could result in secondary damage
or accidents.
252
DANGER
WARNING
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
Booksize Power Units