Siemens SINAMICS S120 Equipment Manual page 484

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Service and Support Booksize
9.3 Forming the DC link capacitors
Date of manufacture
The date of manufacture can be determined from the following assignment to the serial
number (e.g. T-S92067000015):
Table 9-1
Production year and month
Character
S
T
U
V
The serial number is found on the rating plate.
When DC link capacitors are formed, a defined voltage is connected to them and a defined
current flows so that the appropriate capacitor characteristics are re-established for them to
be re-used as DC link capacitors.
Components for the forming circuit (recommendation)
● 1 fuse switch 3-phase 400 V / 10 A
● 3 incandescent lamps 230 V / 100 W
● Various small components, such as lamp socket, cable 1.5 mm
Note
Line Modules must be enabled from the connected Motor Module.
484
Year of manufacture
2004
2005
2006
2007
DANGER
Dangerously high voltage levels are still present in the cabinet up to 5 minutes after it
has been disconnected due to the DC link capacitors. It is only permissible to work on
the equipment or at the DC link terminals after this time has expired.
Character
1 to 9
O
N
D
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
Month of manufacture
January to September
October
November
December
, etc.
2
Booksize Power Units

Advertisement

Table of Contents
loading

Table of Contents