Line Connection Booksize
2.8 Basic Line Filter for Smart Line Modules
Line voltage 415 V 3 AC to 480 V AC + 10 %
● Controlled DC link voltage required, or
● limitation of the DC link voltage required due to motor isolation
2.8.3.2
Line/power connection
Table 2-16
Type of connection
Terminals
Line supply connection (line supply)
Load connection (load)
Basic Line Filter for Smart Line Modules
5 kW
10 kW
16 kW
36 kW
1) for ring cable lugs to DIN 46234
70
Designations
L1, L2, L3, PE
L1´, L2´, L3´, PE
Screw terminal: 10 mm
3-pin/1.5 -1.8 Nm (see Screw Terminals chapter)
2
Grounding bolt: M6/6 Nm
Screw terminal: 35 mm
2
Grounding bolt: M6/6 Nm
1)
1)
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
Booksize Power Units