Functions
9.3 Power output control
The following soft start variants can be configured in order to adapt to the conditions of the
application:
Soft start
Adaptive soft start
With adaptive soft start, the phase angle is adjusted during runtime at the available radiators
so that tripping of the fuse is avoided but the maximum possible start-up speed is reached.
The duration of the soft start thus depends on the radiator used. While with half-wave
control, the soft start only ends with a complete half-wave, phase control is already ended
when the specified setpoint value is reached. If the soft start is not possible, an error
message is generated. The radiator can thus not be operated on the POM.
9.3.4

Switch on heating

To control the power outputs, the heating must first be activated. This is done via the cyclic
data.
Heating status Meaning
On
Off
110
Description
variant
1
Time-optimized variant of the soft start, enabling the heating elements to be warmed
up very quickly.
The time required for one channel is about 100 ms.
2
Slower variant of the soft start that ensures the heating element is not unduly loaded.
The time required for one channel is about 2 seconds.
3
Reserved for future variant, currently corresponds to variant 2.
Channels are activated
Channels are deactivated.
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005