Causes of error and possible solutions
Error code
5104
5105
5106
5107
5109
510B
510E
5113
5114
5117
5118
5119
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
Description
Channel fault: Triac break-
down
"Breakdown" means the triac
is defective and conducts
continuously even without
being activated.
This fault can only be de-
tected if the power output is
switched off. For a 100%
setpoint, the fault can be
neither detected
nor indicated.
Channel fault: Fuse tripped
or triac has high resistance
Incoming fuse has tripped
Channel fault: Defective
heating element/radiator wire
Switch-off threshold for in-
ternal device temperature
At least one voltage is not
connected
Rotating field fault
Channel fault: Partial load
failure
Channel fault: Current load
too high
Channel fault:
Power setpoint is not
reached
Channel fault:
Fault current too high
Channel fault:
Adaptive soft start cannot be
ended
Process and system messages, error handling
11.2 Power Output Module (POM)
Possible causes / Corrective action
Triac is defective → Return POM
•
Switch off machine, check fuse, cabling and heat-
•
ing element and rectify fault, restart
Triac is defective → Return POM
•
Switch off machine, check incoming fuse, cabling
•
and heating element and rectify fault, restart
Switch off machine, check cabling and heating
•
element and rectify fault, restart
For POM4320 Highend with "connection between
•
"phase and phase" (external fuse)" also check in-
coming fuse
Trip threshold overshot: The heating is switched off
automatically by the device.
Actions:
Check function of the fan
•
Switch off the machine, rectify the fault
•
(e.g. cooling malfunction), restart
Check voltage supply and cabling
•
Connect the missing voltage
•
Switch off the machine.
•
Check cabling and heating elements
•
Rectify fault
•
Restart
•
Check setpoint value specification
•
Check heating element
•
Check heating element
•
Check heating element and, if needed, have
•
looked at by Siemens
147