Technical specifications
13.3 Technical Specifications POM4320 Highend
Article number
EMC
EMC interference emission
Electrostatic discharge acc. to IEC
61000-4-2
Field-related interference acc. to IEC
61000-4-3
Conducted interference due to burst
acc. to IEC 61000-4-4
Conducted interference due to surge
acc. to IEC 61000-4-5
Conducted interference due to high-
frequency radiation acc. to IEC 61000-
4-6
Degree and class of protection
IP degree of protection
Standards, approvals, certificates
Reference designation according to
DIN EN 81346-2
Ambient conditions
Ambient temperature during operation
•
•
Ambient temperature during stor-
age/transportation
•
•
•
•
Air pressure acc. to IEC 60068-2-13
•
•
•
•
Altitude during operation relating to sea
level
•
Relative humidity
•
•
180
min.
max.
Storage, min.
Storage, max.
Transportation, min.
Transportation, max.
Operation, min.
Operation, max.
Storage, min.
Storage, max.
Installation altitude above sea level,
max.
Operation at 25 ℃, max.
Operation at 50 ℃, max.
6BK1943-2AH00-0AA0
Limit value in accordance with IEC 61000-6-4:2007 +
A1:2011
4 kV contact discharge / 8 kV air discharge
10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m
(2.0 ... 2.7 GHz)
2 kV power supply lines, 2 kV load lines
on supply and load lines: 1 kV symmetric, 2 kV unsym-
metric
10 V (0.15 ... 80 MHz)
IP20
Q
0 °C
55 °C
-25 °C
70 °C
-25 °C
70 °C
860 hPa
1 080 hPa
660 hPa
1 080 hPa
2 000 m
95 %
50 %; 95 % at 25 °C, decreasing linearly to 50 % at 50
°C
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
6BK1943-2CH00-0AA0