Technical specifications
13.4 Technical specifications for I/O module
Article number
EMC
EMC interference emission
Electrostatic discharge acc. to IEC 61000-4-2
Field-related interference acc. to IEC 61000-4-
3
Conducted interference due to burst acc. to
IEC 61000-4-4
Conducted interference due to surge acc. to
IEC 61000-4-5
Conducted interference due to high-frequency
radiation acc. to IEC 61000-4-6
Degree and class of protection
IP degree of protection
Standards, approvals, certificates
Reference designation according to DIN EN
81346-2
Ambient conditions
Ambient temperature during operation
Ambient temperature during stor-
age/transportation
Air pressure acc. to IEC 60068-2-13
Altitude during operation relating to sea level
Relative humidity
190
min.
max.
Storage, min.
Storage, max.
Transportation, min.
Transportation, max.
Operation, min.
Operation, max.
Storage, min.
Storage, max.
Installation altitude above sea level, max.
Operation at 25 ℃, max.
Operation at 50 ℃, max.
6BK1900-0AA00-0AA0
Limit value in accordance with IEC 61000-6-
4:2007 + A1:2011
4 kV contact discharge / 8 kV air discharge
10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0
GHz), 1 V/m (2.0 ... 2.7 GHz)
2 kV signal lines
Not applicable
10 V (0.15 ... 80 MHz)
IP20
K
0 °C
55 °C
-25 °C
70 °C
-25 °C
70 °C
860 hPa
1 080 hPa
660 hPa
1 080 hPa
2 000 m
95 %
50 %; 95 % at 25 °C, decreasing linearly to 50 %
at 50 °C
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005