Configuring/Programming
8.3 Device/hardware configuration in the TIA Portal
Description
Total power rating (setting per channel) •
Maximum permitted deviation from
total power (setting per channel)
Note
Scaling the total power for parallel connection of loads
• For a connection of the load between phase and neutral conductor, the power ratings to
be configured must be scaled to 230 V.
• For a connection of the load between phase and phase, the power ratings to be
configured must be scaled to 400 V.
Calculation example for interconnection of phase - neutral conductor
Scaling:
P
scaled
Load with U
P
scaled
P
scaled
Calculation example for interconnection of phase - phase
Scaling:
P
scaled
Load with U
P
scaled
P
scaled
88
= P
* (230 V/U
)
2
load
load
= 240 V; P
rated
rated
= 1500 W * (230 V/240 V)
= 1378 W
= P
* (400 V/U
)
2
load
load
= 480 V; P
rated
rated
= 6000 W * (400 V/480 V)
= 4167 W
Value range
500 W to 28,800 W
100 W to 8,000 W
= 1500 W
2
= 6000 W
2
Operating Instructions, 10/2019, A5E35452705A/005
SIPLUS HCS4300 PROFINET/PROFIBUS DP