System overview

2.9 System structure

Option code
Brief description of option
M83
DC busbar system (Id = 2150 A, 2x 60 x 10 mm)
M84
DC busbar system (Id = 2730 A, 2x 80 x 10 mm)
M85
DC busbar system (Id = 3320 A, 2x 100 x 10 mm)
M86
DC busbar system (Id = 3720 A, 3x 80 x 10 mm)
M87
DC busbar system (Id = 4480 A, 3x 100 x 10 mm)
M90
Crane transport assembly (top-mounted)
N52
DC link fuses for Basic Line Module
P10
Measuring instrument for line values (installed in the cabinet door)
P11
Measuring instrument for line variables with PROFIBUS connection, installed in the cabinet door
T58
Rating plate data in English/French
T60
Rating plate data in English/Spanish
T80
Rating plate data in English/Italian
Y09
Special paint finish for cabinet
Y11
Factory assembly into transport units
Y31
One-line label for plant identification, 40 x 80 mm
Y32
Two-line label for plant identification, 40 x 180 mm
Y33
Four-line label for plant identification, 40 x 180 mm
2.9
System structure
Line Modules are coupled with the various Motor Modules using prefabricated DC busbar
sets with different current load ratings.
An auxiliary power supply system spanning the individual Cabinet Modules supplies the
required auxiliary voltages for the equipment fans and the 24 V DC loads.
Communication between the Control Unit, Line Module and Motor Module, and other active
SINAMICS components takes place via DRIVE-CLiQ connections.
DRIVE-CLiQ is an internal serial interface of the drive that enables fast and easy
configuration of the complete drive line-up with prefabricated cables in varying lengths.
As an option, Cabinet Modules can be delivered in preconfigured transport units with a total
width of up to 2,400 mm each. This option is recommended in particular for Line Modules
together with Line Connection Modules since, in this case, the Line Connection Module must
be equipped with a pre-charging DC link or line reactors (depending on the type of Line
Module), in addition to the electrical interface (mounted on a busbar).