X41 Ep Terminal / Temperature Sensor Connection - Siemens SINAMICS S120 Manual

Cabinet modules
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options
8.20 K90, Control Unit CU320-2 DP
8.20.4.2

X41 EP terminal / temperature sensor connection

Table 8- 18
Terminal block X41 on the customer terminal block X55
Terminal
1
2
3
4
Max. connectable cross-section: 2.5 mm
Risk of electric shock!
Only temperature sensors that meet the safety isolation specifications stipulated in
EN 61800-5-1 may be connected to terminals "+Temp" and "-Temp". If safe electrical
separation cannot be guaranteed (for linear motors or third-party motors, for example), a
Sensor Module External (SME120 or SME125) must be used.
Failure to observe these instructions can result in electric shock!
Note
Connectable sensor
The following sensors can be connected to the temperature sensor connection:
KTY84-1C130 / PTC / PT100
NOTICE
Use shielded cables
The temperature sensor connection must be shielded. The shielding must be attached to
the shield support of the Motor Module.
Note
KTY temperature sensor connected with the correct polarity
The KTY temperature sensor must be connected with the correct polarity.
If the polarity is reversed, the sensor will not be able to detect if the motor overheats.
424
Function
Technical data
EP M1
Supply voltage: 24 V DC (20.4 V - 28.8 V)
(Enable Pulses)
Current consumption: 10 mA
EP +24 V
Signal propagation times:
(Enable Pulses)
L → H: 100 μs;
H → L: 1000 μs
The pulse inhibit function is only available when Safety Integrated Basic
Functions are enabled.
- Temp
Temperature sensor connection for motor temperature measurement:
KTY84-1C130, PTC, PT100
+ Temp
2
DANGER
Cabinet Modules
Manual, 03/2013, A5E03263538A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents