Siemens SINAMICS S120 Manual page 506

Cabinet modules
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options
8.39 L55, cabinet anti-condensation heating
X240 connection for cabinet anti-condensation heating
Table 8- 62
Terminal
1
2
3
Max. connectable cross-section: 4 mm²
Hazardous electrical voltage
Since the voltage is supplied from an external source, voltage may still be present in all of
the cabinets even when the main switches in all units are open.
You must observe the "five safety rules" when carrying out maintenance work.
Note
Temperature-controlled supply voltage
The supply voltage can be provided by means of a temperature control, to prevent the anti-
condensation heating unnecessarily operating at a higher ambient temperature.
504
Terminal block X240
Designation
L1
N
PE
DANGER
Technical data
110 to 230 V AC voltage supply
Current demand:
- min.: approx. 0.43 A (for 230 V AC, 100 W)
- max.: approx. 1.8 A (for 110 V AC, 200 W)
Protective conductor
Cabinet Modules
Manual, 03/2013, A5E03263538A