Diagnostics/Service
8.5 Remote diagnosis "RCS Host Embedded / RCS Viewer Embedded"
8.5.1

Configuring "RCS Host Embedded"

Adapting NCU 7x0 to router (VPN network)
NCU 7x0 (Ethernet interface X130) and router are connected via an Ethernet cable.
Adapt the network configuration of the NCU 7x0 to the configuration of the Ethernet interface
of the router.
1. If the NCU 7x0 is already located on the network, save the current network configuration.
2. Start the machine.
3. Press the "Startup" -> "HMI" -> "Network Config." softkeys.
4. Entries:
5. Configuration of the Ethernet interface "Router NCU 7x0"
6. The following entries are predefined when the router is configured and are only used as
examples in the above illustration.
7. Press the "Save" softkey. The NCU 7x0 restarts.
126
– IP address
– Subnet mask
– Gateway
Commissioning HMI-Embedded (IM2)
Commissioning Manual, 01/2008, 6FC5397-8CP10-1BA0