Commissioning the cooling circuit
5.3 Filling the internal deionized water circuit
5.3.1
Venting the cooling circuit
5.3.1.1
Venting the pump
First vent the pumps of the Heat Exchanger Module (
The precise position of the vent screw can be taken from the layout diagrams provided.
Figure 5-1
5.3.1.2
Venting the components
General information on venting components
The hose for venting the following components can be found in the cabinet. Release the vent
hose
Figure 5-2
Continue venting the component until clear cooling liquid escapes in a continuous stream.
122
Example: Vent screw of the pump
②
from the cabinet frame. Hold the vent hose outside the cabinet in a bucket.
Vent hose
①
).
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A