6.1.2.4

DRIVE-CLiQ interfaces X400, X401, X402

Table 6- 7
DRIVE-CLiQ interfaces X400, X401, X402
PIN
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
6.1.2.5

Terminal block -X40 external 230 V AC auxiliary infeed

Terminal block -X40 provides you with the option of connecting an external auxiliary infeed
(such as an uninterruptible power supply) that is independent of the main infeed. The
connection may be protected with up to a 16 A fuse.
Table 6- 8
Terminal
1
2
5
6
Max. connectable cross-section: 2.5 mm²
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Terminal block X40 external 230 VAC auxiliary infeed
Designation
L1
L1
N
N
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
Technical data
Factory-installed jumper to terminal 2; this jumper must be re-
moved if an external infeed is used.
Connection of external 230 VAC auxiliary infeed: L1
Factory-installed jumper to terminal 6; this jumper must be re-
moved if an external infeed is used.
Connection of external 230 VAC auxiliary infeed: N
Cabinet Modules
6.1 Basic Line Connection Modules
141