G51 To G54, Temperature Sensor Module Tm150; General Information - Siemens SINAMICS S120 Manual

Cabinet modules liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options

9.5 G51 to G54, temperature sensor module TM150

9.5
G51 to G54, temperature sensor module TM150
9.5.1

General information

Availability of option
These options are available for the following S120 Cabinet Modules:
● Basic Line Connection Module
● Active Line Connection Module
Description
The Terminal Module TM150 is used for acquiring and evaluating several temperature
sensors.
In this case, option G51 is for 1 temperature sensor module, option G52 for 2 temperature
sensor modules TM150 etc.:
● G51: 1 temperature sensor module TM150
● G52: 2 temperature sensor modules TM150
● G53: 3 temperature sensor modules TM150
● G54: 4 temperature sensor modules TM150
The temperature is measured in a temperature range from -99° C to +250° C for the
following temperature sensors:
● PT100 (with monitoring for wire breakage and short-circuit)
● PT1000 (with monitoring for wire breakage and short-circuit)
● KTY84 (with monitoring for wire breakage and short-circuit)
● PTC (with short-circuit monitoring)
● Bimetallic NC contact (without monitoring)
For the temperature sensor inputs, for each terminal block the evaluation can be
parameterized for 1x2-wire, 2x2-wire, 3-wire or 4-wire. There is no galvanic isolation in the
TM150.
A maximum of 12 temperature sensors can be connected to Terminal Module TM150.
290
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A

Advertisement

Table of Contents
loading

Table of Contents