5.3.2.1
Control and status signals at the TM31 Terminal Module
Commands for controlling the cooling unit
The following commands are isolated signals from the converter to the cooling unit:
Command
Switching on and switching off the cooling unit
•
•
Stopping the cooling unit
•
Acknowledging the cooling unit alarms
•
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
If the cooling unit is in the ready state, then it
is switched on with a rising signal edge.
The cooling unit is switched off with a falling
signal edge. The pump continues to run for x
minutes.
The cooling unit is immediately switched off
with a falling signal edge. The pump does not
continue to run.
Alarms and fault signals of the cooling unit are
acknowledged with a rising signal edge.
Commissioning the cooling circuit
5.3 Filling the internal deionized water circuit
Function name
DI/DO8
DI/DO9
DI/DO10
TM31 terminal
-X541:2
-X541:3
-X541:4
129