Diagnostic System; Status Information; Warnings; Main - Siemens SIMOCRANE Operating Instructions Manual

Energy storage system management v01.01
Table of Contents

Advertisement

Diagnostic system

The SIMOCRANE ESSM Step 7 library includes a comprehensive diagnostic system which signals
system states to the higher-level crane control system and the local operator interface. The
diagnostic system consists of status information, warnings and fault messages. You can find an
overview of the telegrams and the meanings of the individual bits below.
7.1

Status information

See chapter outSendToMaster (Page 56): StatusWord 1 - StatusWord 3.
7.2

Warnings

7.2.1

Main

Bit 0
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 1
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 2
Message class
Component
Response
SIMOCRANE Energy Storage System Management V01.01
Operating Instructions, 04/2023, A5E51573536B AE
Chargepower setpoint < 0 kW -> Limited to 0 kW
Warning
Setpoint input
Limitation of setpoint to 0 kW
Self-acknowledging
A charge power limit < 0 kW has been detected
Enter a limit > 0 kW
Dischargepower setpoint < 0kW -> Limited to 0 kW
Warning
Setpoint input
Limitation of setpoint to 0 kW
Self-acknowledging
A discharge power limit < 0 kW has been detected
Enter a limit > 0 kW
DC-Link Voltage setpoint in mode PS < 500.0 V -> Limited to 500.0 V
Warning
Setpoint input mode: "Peak Shaving"
Limitation of setpoint to 500.0 V
7
99