Sequencer - Siemens SIMOCRANE Operating Instructions Manual

Energy storage system management v01.01
Table of Contents

Advertisement

Bits 10-31
-
7.2.4

Sequencer

Bit 0
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 1
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 2
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 3
Message class
Component
Response
Acknowledgement
Cause
Remedy
SIMOCRANE Energy Storage System Management V01.01
Operating Instructions, 04/2023, A5E51573536B AE
Spare
-
Start - Up aborted by operator
Warning
Control
Start is aborted
Self-acknowledging
A start procedure has been aborted by a stop command
Do not stop the ESS until startup is complete
No drive selected
Warning
Control
Start is blocked on start trigger
Self-acknowledging
No SINAMICS DCP has been selected for startup
Select at least one device for startup
Battery not ready
Warning
Battery
Start is blocked on start trigger
Self-acknowledging
Operating state of battery not ready
Commission the battery correctly
Main breaker is open
Warning
Switchgear
Start is blocked on start trigger
Self-acknowledging
Main breaker is open
Close the main breaker before startup
Diagnostic system
7.2 Warnings
103

Advertisement

Table of Contents
loading

Table of Contents