Siemens SIMOCRANE Operating Instructions Manual page 106

Energy storage system management v01.01
Table of Contents

Advertisement

Diagnostic system
7.2 Warnings
Bit 4
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 5
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 6
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 7
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bits 8-31
-
104
VDC too low for selected mode
Warning
SINAMICS DC link
Start is blocked on start trigger
Self-acknowledging
Measured DC link voltage too low for current operating mode
Change the operating mode or adjust the DC link voltage
VDC too high for selected mode
Warning
SINAMICS DC link
Start is blocked on start trigger
Self-acknowledging
Measured DC link voltage too high for current operating mode
Change the operating mode or adjust the DC link voltage
Battery current limit < recommended start current (50 A)
Warning
Battery
Limitation of start current to the current permitted by the battery
Self-acknowledging
The battery current is < 50 A
Check whether the battery current is limited by the battery and that it is correctly
transferred
Battery current limit < min start current
Warning
Battery
Start is blocked on start trigger
Self-acknowledging
The battery current is too low
Check whether the battery current is limited by the battery and that it is correctly
transferred
Spare
-
SIMOCRANE Energy Storage System Management V01.01
Operating Instructions, 04/2023, A5E51573536B AE