Energy storage system management v01.01
Table of Contents

Advertisement

Control and engineering
6.2 Control via remote PLC
Figure 6-5
Emergency start
In order to ensure operation despite the presence of one or more faulted SINAMICS DCPs, the
faulted devices can be deselected. The faulted SINAMICS DCPs must then be disconnected
from all power sources. After this, the "DCDCUnitxDisconn" bit must be set for each
disconnected power converter. After an acknowledgement, operation can be continued with
the remaining power converters despite the presence of a faulted device. The total power is
reduced as a consequence.
74
Correct startup of ESS in "Manual Mode"
SIMOCRANE Energy Storage System Management V01.01
Operating Instructions, 04/2023, A5E51573536B AE